За участие в процедура публично състезание за възлагане на обществена поръчка


(8.3.3.6) Auto-reclosure indications in monitor direction



страница8/22
Дата08.06.2018
Размер3.95 Mb.
#72713
1   ...   4   5   6   7   8   9   10   11   ...   22

(8.3.3.6) Auto-reclosure indications in monitor direction







INF

Semantics






<128>

CB ‘on’ by AR


















<129>

CB ‘on’ by long-time AR


















<130>

AR blocked

(8.3.3.7) Measurands in monitor direction







INF

Semantics









<144>

Measurand I
























<145>

Measurands I, V


















<146>

Measurands I, V, P, Q


















<147>

Measurands IN, VEN


















<148>

Measurands IL1,2,3, VL1,2,3, P, Q, f

(8.3.3.8) Generic functions in monitor direction







INF

Semantics









<240>

Read headings of all defined groups


















<241>

Read values or attributes of all entries of one group


















<243>

Read directory of a single entry


















<244>

Read value or attribute of a single entry


















<245>

End of general interrogation of generic data


















<249>

Write entry with confirmation


















<250>

Write entry with execution


















<251>

Write entry aborted

(8.3.4) Selection of standard information numbers in control direction

(8.3.4.1) System functions in control direction







INF

Semantics






<0>

Initiation of general interrogation


















<0>

Time synchronization

Notes:

The general interrogation to the subordinated devices is send directly after the initialization of the RTU and on every change of the subordinated link from state OFFLINE to state ONLINE. Initiation of general interrogation is send as global function-type GLB (value 255)



The time synchronization command is only send to subordinated devices which are in state ONLINE, and only if the time tag of the own RTU is valid (synchronized). Time synchronization is sent as global function-type GLB (value 255)

(8.3.4.2) General commands in control direction







INF

Semantics






<16>

Auto-recloser on/off


















<17>

Teleprotection on/off


















<18>

Protection on/off


















<19>

LED reset


















<23>

Activate characteristic 1


















<24>

Activate characteristic 2


















<25>

Activate characteristic 3


















<26>

Activate characteristic 4

(8.3.4.3) Generic functions in control direction







INF

Semantics









<240>

Read headings of all defined groups


















<241>

Read values or attributes of all entries of one group


















<243>

Read directory of a single entry


















<244>

Read value or attribute of a single entry


















<245>

General interrogation of generic data


















<248>

Write entry


















<249>

Write entry with confirmation


















<250>

Write entry with execution


















<251>

Write entry abort

(8.3.5) Basic application functions






Test mode















Blocking of monitor direction















Disturbance data















Generic services















Private data

NOTE: Type Identifications:




  • 1 and 2 in monitor direction

  • 20 in control direction

(8.3.6) Miscellaneous

Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in 7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No differ­ent rating shall be used in ASDU 3 and ASDU 9, i.e. for each measurand there is only one choice.




Measurand

Max. MVAL = rated value times

1,2 or 2,4
















Current L1


























Current L2


























Current L3


























Voltage L1-E


























Voltage L2-E


























Voltage L3-E


























Active power P


























Reactive power Q


























Frequency f


























Voltage L1 - L2











5. Комплектност на предложението

Участникът е длъжен да представи в своето предложение следната техническа документация:

● Технически характеристики съгласно Таблица № 7, Таблица № 8 и Таблица № 9;

● Протоколи или сертификат (в който да бъдат цитирани всички стандарти) от типови изпитвания на защитите, на хартиен или електронен носител, извършени в акредитирана или специализирана по изискванията на IEC и ISO (или еквивалентен) лаборатория, на български език. Допуска се при липса на превод на български език, същите да се представят на английски език;

● Декларация за съответствие от производителя за комуникация на предлаганите защити по протокол съгласно IEC 60870–5–103, придружена с доказателства (на хартиен или електронен носител) за изпълнение на изискванията от т.5;

● Описание и схеми на трансформаторните аналогови входове (по т. 2.1.3 и 2.2.4 от таблица № 7, таблица № 8 и по т. 2.3 от таблица № 9) с тип и преобразуване на аналоговите величини в цифрови;

● Описание и разпределение на входните трансформаторни преобразуватели, цифрови входове и изходи, комуникационни портове, захранващ модул и др. по платки и слотове;

● Инструкции за монтаж, настройка, въвеждане и експлоатация на хартиен или електронен носител на устройствата на български език. Допуска се при липса на превод на български език, същите да се представят на английски език;

● Попълнен лист за поръчка (Ordering sheet) на предлаганите типове устройства;

● Документи на хартиен или електронен носител, доказващи параметрите на декларираните (посочените) технически данни, каталози, проспекти или технически данни на изделието от фирмата производител.