(8.3.3.6) Auto-reclosure indications in monitor direction
|
|
INF
|
Semantics
|
|
|
<128>
|
CB ‘on’ by AR
|
|
|
|
|
|
|
<129>
|
CB ‘on’ by long-time AR
|
|
|
|
|
|
|
<130>
|
AR blocked
|
(8.3.3.7) Measurands in monitor direction
|
|
INF
|
Semantics
|
|
|
|
<144>
|
Measurand I
|
|
|
|
|
|
|
|
|
<145>
|
Measurands I, V
|
|
|
|
|
|
|
<146>
|
Measurands I, V, P, Q
|
|
|
|
|
|
|
<147>
|
Measurands IN, VEN
|
|
|
|
|
|
|
<148>
|
Measurands IL1,2,3, VL1,2,3, P, Q, f
|
(8.3.3.8) Generic functions in monitor direction
|
|
INF
|
Semantics
|
|
|
|
<240>
|
Read headings of all defined groups
|
|
|
|
|
|
|
<241>
|
Read values or attributes of all entries of one group
|
|
|
|
|
|
|
<243>
|
Read directory of a single entry
|
|
|
|
|
|
|
<244>
|
Read value or attribute of a single entry
|
|
|
|
|
|
|
<245>
|
End of general interrogation of generic data
|
|
|
|
|
|
|
<249>
|
Write entry with confirmation
|
|
|
|
|
|
|
<250>
|
Write entry with execution
|
|
|
|
|
|
|
<251>
|
Write entry aborted
|
(8.3.4) Selection of standard information numbers in control direction
(8.3.4.1) System functions in control direction
|
|
INF
|
Semantics
|
|
|
<0>
|
Initiation of general interrogation
|
|
|
|
|
|
|
<0>
|
Time synchronization
|
Notes:
The general interrogation to the subordinated devices is send directly after the initialization of the RTU and on every change of the subordinated link from state OFFLINE to state ONLINE. Initiation of general interrogation is send as global function-type GLB (value 255)
The time synchronization command is only send to subordinated devices which are in state ONLINE, and only if the time tag of the own RTU is valid (synchronized). Time synchronization is sent as global function-type GLB (value 255)
(8.3.4.2) General commands in control direction
|
|
INF
|
Semantics
|
|
|
<16>
|
Auto-recloser on/off
|
|
|
|
|
|
|
<17>
|
Teleprotection on/off
|
|
|
|
|
|
|
<18>
|
Protection on/off
|
|
|
|
|
|
|
<19>
|
LED reset
|
|
|
|
|
|
|
<23>
|
Activate characteristic 1
|
|
|
|
|
|
|
<24>
|
Activate characteristic 2
|
|
|
|
|
|
|
<25>
|
Activate characteristic 3
|
|
|
|
|
|
|
<26>
|
Activate characteristic 4
|
(8.3.4.3) Generic functions in control direction
|
|
INF
|
Semantics
|
|
|
|
<240>
|
Read headings of all defined groups
|
|
|
|
|
|
|
<241>
|
Read values or attributes of all entries of one group
|
|
|
|
|
|
|
<243>
|
Read directory of a single entry
|
|
|
|
|
|
|
<244>
|
Read value or attribute of a single entry
|
|
|
|
|
|
|
<245>
|
General interrogation of generic data
|
|
|
|
|
|
|
<248>
|
Write entry
|
|
|
|
|
|
|
<249>
|
Write entry with confirmation
|
|
|
|
|
|
|
<250>
|
Write entry with execution
|
|
|
|
|
|
|
<251>
|
Write entry abort
|
(8.3.5) Basic application functions
NOTE: Type Identifications:
-
1 and 2 in monitor direction
-
20 in control direction
(8.3.6) Miscellaneous
Measurands are transmitted with ASDU 3 as well as with ASDU 9. As defined in 7.2.6.8, the maximum MVAL can either be 1,2 or 2,4 times the rated value. No different rating shall be used in ASDU 3 and ASDU 9, i.e. for each measurand there is only one choice.
Measurand
|
Max. MVAL = rated value times
1,2 or 2,4
|
|
|
|
|
|
Current L1
|
|
|
|
|
|
|
|
|
|
Current L2
|
|
|
|
|
|
|
|
|
|
Current L3
|
|
|
|
|
|
|
|
|
|
Voltage L1-E
|
|
|
|
|
|
|
|
|
|
Voltage L2-E
|
|
|
|
|
|
|
|
|
|
Voltage L3-E
|
|
|
|
|
|
|
|
|
|
Active power P
|
|
|
|
|
|
|
|
|
|
Reactive power Q
|
|
|
|
|
|
|
|
|
|
Frequency f
|
|
|
|
|
|
|
|
|
|
Voltage L1 - L2
|
|
|
|
|
5. Комплектност на предложението
Участникът е длъжен да представи в своето предложение следната техническа документация:
● Технически характеристики съгласно Таблица № 7, Таблица № 8 и Таблица № 9;
● Протоколи или сертификат (в който да бъдат цитирани всички стандарти) от типови изпитвания на защитите, на хартиен или електронен носител, извършени в акредитирана или специализирана по изискванията на IEC и ISO (или еквивалентен) лаборатория, на български език. Допуска се при липса на превод на български език, същите да се представят на английски език;
● Декларация за съответствие от производителя за комуникация на предлаганите защити по протокол съгласно IEC 60870–5–103, придружена с доказателства (на хартиен или електронен носител) за изпълнение на изискванията от т.5;
● Описание и схеми на трансформаторните аналогови входове (по т. 2.1.3 и 2.2.4 от таблица № 7, таблица № 8 и по т. 2.3 от таблица № 9) с тип и преобразуване на аналоговите величини в цифрови;
● Описание и разпределение на входните трансформаторни преобразуватели, цифрови входове и изходи, комуникационни портове, захранващ модул и др. по платки и слотове;
● Инструкции за монтаж, настройка, въвеждане и експлоатация на хартиен или електронен носител на устройствата на български език. Допуска се при липса на превод на български език, същите да се представят на английски език;
● Попълнен лист за поръчка (Ordering sheet) на предлаганите типове устройства;
● Документи на хартиен или електронен носител, доказващи параметрите на декларираните (посочените) технически данни, каталози, проспекти или технически данни на изделието от фирмата производител.